How a surge protector works: Principles and protection

Understanding how a surge protector works will help you decide whether to install one and how to set it up. The following sections describe its operating principle, its connection to the panel, types 1, 2, and 3, the cases in which the standard requires its use, its limitations, and the signs that indicate it needs to be replaced.


How does a surge protector detect and divert a power surge?

A surge protector does not cut off the power. He reacts in a fraction of a second: he diverts some of the energy from a voltage spike to ground. The difference lies in the speed of this reaction and the voltage that still reaches the devices.

Deux techniciens en formation inspectant un tableau électrique, l’un pointe un composant au doigt tandis que l’autre tient un

What is a surge protector used for?

The function of a surge arrester is to limit transient overvoltages—that is, very brief voltage spikes. As a result, the voltage reaching the home's electrical circuits and equipment remains lower. These spikes have several causes:

  • Distant lightning: A strike anywhere near a residence is enough to create a power surge that spreads through the power grid.
  • Switching surges: Switching operations on the power grid also generate them.
  • Devices on display: Appliances, computers, and the internet router receive everything that hasn't been clipped.

What happens when the tension rises?

Under normal operating conditions, the surge arrester remains inactive: it allows only a minimal leakage current to pass through. As soon as a voltage surge exceeds its threshold, its protective component becomes conductive. It then creates a path of low resistance that diverts part of the pulse current to ground, according to its wiring diagram.

This transition relies on two internal technologies. Spark gaps operate on the principle of ignition: an arc is established when the voltage exceeds a certain threshold. Conversely, varistors and diodes operate by clipping: they cut off the peak of the voltage waveform.

How is the voltage limited?

By limiting voltage surges between conductors, the device maintains the voltage at a level compatible with the equipment's surge resistance. It does not eliminate all the voltage spikes. Two values describe this behavior: Uc, the maximum allowable continuous voltage, and Up, the voltage protection level. Under identical conditions, a lower Up value indicates better limitation, but it alone does not describe the level of protection achieved once the device is connected.

The current-carrying capacity completes this data: In denotes the rated discharge current, Imax the maximum current for type 2, and Iimp the pulse current for type 1. Some type 2 series have Imax values of 15, 40, or 65 kA. Combined models specify Iimp values of 12.5 or 25 kA, although these values may not be suitable for all cases. DomeaShop combines these levels intoits selection of lightning arresters and surge protectors.

Why does the connection affect the effectiveness of the surge arrester?

Even a well-chosen appliance loses some of its effectiveness if it is connected incorrectly. There are three key factors to consider in an electrical installation: the location of the surge arrester, the length of its conductors to ground, and how it is isolated in the event of a fault.

Boîtier mural avec quatre interrupteurs secteur gris et petits voyants verts.

Where should the protective covering be placed in the home?

The main surge arrester is installed in the electrical panel at the point of entry of the system, as close as possible to the power supply and the ground. According to NF C 15-100-1 (the French standard that establishes general rules for electrical installations), a surge protector that protects the entire residence must be installed immediately downstream from the main circuit-breaking device.

The distance to the devices is then taken into account. In its 2024 edition, NF C 15-100-10 (the section of the standard devoted to residential buildings) recommends additional protection when equipment is located more than 10 m from the main surge arrester. This distance does not apply to the length of the connecting wires. DomeaShop offers modular surge protectors for electrical panels as well as surge protectors designed to be placed near sensitive equipment.

Why shorten the ground connection?

The surge arrester must be properly connected to the ground terminal and to the equipotential bonding system, which brings the metal structures in the dwelling to the same potential. A good ground connection does not compensate for conductors that are too long or improperly routed: these increase the residual voltage reaching the devices. In practice, the installation guideline specifies a maximum length of 50 cm for the connection run, to be adjusted according to the diagram and the equipment specifications.

The conductor's cross-sectional area matters, too. A guide in NF C 15-100-10 specifies a minimum of 6 mm² of copper or equivalent for a type 2. This minimum increases to 16 mm² for type 1. Connect the ground terminal to the panel's terminal block using the shortest possible route, after connecting the phase and neutral wires. The single-phase and three-phase models ofthe Hager line of modular surge protectors must also be connected to a properly grounded system.

Why is it necessary to provide for the disconnection of the surge arrester?

After being subjected to heavy loads, a surge arrester can deteriorate to the point of failing, particularly by short-circuiting. The disconnect device then isolates the faulty unit. It does not limit the voltage surge where it occurs.

For a non-self-protected model, select a circuit breaker or other external device rated for the expected short-circuit current and coordinated according to the manufacturer's specifications. It must not trip unintentionally during normal operation. A self-protected model includes this feature and does not require a dedicated circuit breaker if the manufacturer's specifications are followed. Still, his condition needs to be monitored.

What types of surge protectors protect a home, and how effective are they?

Surge arresters are classified into three types based on the amount of energy they can dissipate and their location in the system. The appropriate level of electrical protection depends on the building's exposure, its power supply, and the equipment to be protected.

Un homme branche une prise électrique avec une multiprise dans une pièce lumineuse.

What do types 1, 2, and 3 protect against?

Each type is tested with a different current waveform, which reflects the amount of energy it can withstand:

  • Type 1: It diverts high-energy lightning currents, particularly when the building is equipped with external lightning protection. It is tested using a 10/350 µs pulse, and there are combined type 1 and type 2 models available.
  • Type 2: This is the standard protection for a low-voltage circuit when Type 1 protection is not required. It is tested using an 8/20 µs pulse.
  • Type 3: This thin shield is placed near a device and remains synchronized with the head shield.

Type 3 corresponds to what is often called a surge arrester: its lower current-carrying capacity means it cannot replace a type 1 or type 2 device. This may be necessary when sensitive equipment is located far from the distribution panel.

DomeaShop offers Hager models for single-phase and three-phase networks, as well asLegrand type 3 surge protectors.

When is this protection required and appropriate?

NF C 15-100-10 does not require lightning arresters in all residential buildings. It distinguishes zone AQ1, defined by a keraunic level Nk = 25 (number of thunderstorm days per year) or a lightning density Ng = 2.5 (impacts per km² per year), from zone AQ2, defined by Nk > 25 or Ng > 2.5. A building equipped with external lightning protection requires a type 1 system in both zones, with the exception of certain buildings equipped with a transformer substation. A fully underground power supply does not always require a surge arrester. When personal safety is at stake, a risk analysis is required in AQ1, and a surge protector becomes mandatory in AQ2.

The selection then takes into account the power system—for example, whether the surge arrester is single-phase or three-phase—the grounding configuration, Uc, Up, the discharge currents, and coordination with the disconnection. According to AFNOR (the French standards organization), standards NF C 15-100-1 and NF C 15-100-10 are dated august 2024. The revised series will serve as the reference standard starting in september 2025 for new installations and related work. NF EN 61643-11, dated may 2014, is a separate product standard that the models of theLegrand surge protector catalog.

What are its limitations, and how can you check its condition?

Not all types of power surges can be protected against by a conventional surge protector. It handles transient spikes, but not power outages, voltage drops, or temporary overvoltages in the grid, such as those caused by high voltage or a low-voltage neutral break.

Its presence, therefore, does not guarantee absolute protection. After a severe thunderstorm, check its status indicator and make sure it hasn't disconnected. On some models, a red indicator light signals that a cartridge or the entire unit needs to be replaced.

What happens next depends on the device's design: some surge arresters have a replaceable cartridge, while others are one-piece units. Once installation is complete, verify the electrical compatibility of the new equipment, its connections, and its coordination with the power disconnection.

Our team of writers has been selected to provide you with quality articles to help you realize your projects. All information is systematically checked and referenced, so you can be sure of our editorial quality.